Double Check Valve Testing in Montgomeryville, PA

A double check valve assembly, or DCVA, has two independent spring-loaded checks between two resilient-seated shutoffs and four test cocks. It is approved for low-hazard connections, so you see it on many fire lines, apartment services and some irrigation systems.

The tester bleeds and reads each check separately. Each one has to hold a differential of at least 1.0 psid. If a check reads lower, the cause is usually a worn rubber disc, a weak spring or debris across the seat.

Unlike an RPZ, a DCVA can be installed in a pit or vault in many jurisdictions, which brings its own problems. Flooded vaults make test cocks hard to reach and corrode the bolts. Testers often pump the vault before they can start.

Grizzly Backflow & Plumbing connects you with local testers in Montgomeryville, PA for double check valve testing, report filing with your purveyor and repair if a check fails. Good backflow prevention depends on both checks holding, not one. Call (833) 990-5874.

How it works

Four steps to backflow testing in Montgomeryville, PA

  1. 01

    Grab your notice

    Have the utility letter handy. It lists the device, serial number and due date.

  2. 02

    Talk it through

    Call (833) 990-5874. We go over the device type and the price before anything is booked.

  3. 03

    Test day

    A certified tester reads each check and the relief valve on a calibrated gauge.

  4. 04

    Report filed

    The report goes to your water utility, and you keep a copy for your records.

Coverage

Backflow Testing Services Across Montgomeryville, PA

Backflow testing for the neighborhoods and ZIP codes around Montgomeryville, PA.

ZIP codes we serve

18936

Backflow testing FAQs

Questions about backflow testing

Questions we hear most often about Double Check Valve Testing in Montgomeryville, PA.

Talk to a person
What is the difference between an RPZ and a double check valve?
Both have two independent check valves. An RPZ adds a relief valve between the checks that discharges water to atmosphere if the checks leak, which is why it is required on high-hazard connections.
How long does a backflow test take?
A residential PVB or double check test usually takes 20 to 30 minutes. Large commercial and fire line assemblies take longer.
Does my lawn sprinkler system in Montgomeryville, PA need a backflow preventer?
Almost every US plumbing code requires one on irrigation, since fertilizer, pesticide and standing water at the heads can siphon back. The device type depends on local code and how the system is laid out.
What does a failed backflow test mean?
A check valve or the relief valve did not hold its required pressure differential. The device needs repair or replacement, then a retest before a passing report can be filed.
Do I need an expansion tank after installing a backflow preventer?
Often, yes. The device makes your plumbing a closed system, so heated water cannot expand back to the main and the water heater relief valve may start dripping.

Book a backflow test

Backflow Test Due in Montgomeryville, PA? Call now.

Certified testers for backflow testing in Montgomeryville, PA. Call (833) 990-5874 and we go through the device and the price before anything is booked.

(833) 990-5874
Phone · (833) 990-5874
Call (833) 990-5874 Enquire